Start supplies the initial current. The KM1 auxiliary contact maintains the path after Start is released. Stop sits before both branches, so pressing it interrupts the circuit.
1. Get familiar with the circuit before reading the diagram
Imagine controlling a pump with Start and Stop buttons. You want one press of Start to run the pump, rather than holding the button all day.
This example uses a 24 VDC control supply and a compatible KM1 contactor coil. We examine only the coil control circuit; motor power and protection are outside this diagram.
Start is normally open (NO): open when released. Stop is normally closed (NC): closed when released. The KM1 NO auxiliary contact closes when the KM1 coil is energized.
2. Which path carries current when Start is pressed and released?
Pressing Start completes the path: +24 V → Stop → Start → KM1 coil → 0 V. KM1 picks up and closes its auxiliary contact.
Releasing Start opens the button path. A second path is now available: +24 V → Stop → KM1 auxiliary contact → KM1 coil → 0 V. This keeps the coil energized and is called holding or seal-in.
Pressing Stop opens the common supply path to both branches. The coil drops out and its auxiliary contact opens. Releasing Stop does not restart the circuit; you must press Start again.
Look at both ends of the KM1 branch: it bypasses only Start. If it bypasses Stop as well, the circuit may hold but Stop will not interrupt it.
3. Understand the circuit one action at a time
Before any button is pressed, Start and the KM1 auxiliary contact are open, so the coil is unpowered. Start creates the initial supply path; the auxiliary contact then closes to maintain it.
Use the table to compare each action. Pay particular attention to releasing Start and releasing Stop: Start release retains holding, whereas Stop release after stopping leaves the circuit idle.
| Situation | Start / Stop | KM1 |
|---|---|---|
| Power on, no button pressed | Start open, Stop closed | Coil unpowered; holding contact open. |
| Press Start | Start closed, Stop closed | Coil energized; KM1 auxiliary contact closed. |
| Release Start | Start open, Stop closed | Coil fed through the holding contact. |
| Press Stop | Stop open | Common path interrupted; coil drops out and auxiliary contact opens. |
| Release Stop after stopping | Stop closes again | KM1 stays released, waiting for a new Start command. |
4. Build this circuit in EleRun
You do not need many devices to test the principle. Begin with a supply, two buttons, a coil, and an auxiliary contact.
If the coil picks up but the auxiliary contact does not close, inspect the symbol type and linking tag. Do not add wires to compensate for a contact that is not behaving correctly.
- Place Start NO, Stop NC, the KM1 coil, and a NO auxiliary contact.
- Assign the same KM1 tag to the coil and auxiliary contact in device properties.
- Wire the supply through Stop and Start to the coil, then connect the supply return.
- Wire the KM1 auxiliary contact in parallel with Start: branch beginning after Stop and ending before the coil.
- Switch to Run. Press Start, release Start, press Stop, and release Stop. Compare with the table.
5. Try a few more situations to check your understanding
Holding after Start is a useful result, but test stopping and power restoration too. The table lists six scenarios to examine.
Loss of control power releases the coil and opens the holding contact. If power returns with Start released, the coil does not restart automatically. If Start is held or stuck closed, behavior may differ because the Start path remains available.
In this diagram, pressing Start and Stop together opens the common path at Stop, leaving the coil unpowered. If the tool cannot reproduce a particular action directly, trace the current path and explicitly record that it was not simulated.
| Test action | Expected result |
|---|---|
| Apply power without pressing Start | KM1 does not start automatically. |
| Press and release Start | KM1 picks up and continues holding. |
| Press and release Stop | KM1 drops out and does not restart automatically. |
| Remove control power while holding | KM1 drops out; holding contact opens. |
| Restore power with Start released | KM1 does not restart automatically. |
| Press Start and Stop simultaneously | Stop interrupts the common path; KM1 is unpowered. |
6. Three symptoms that point to where you should look
Each fault gives a clue. Inspecting the relevant branch is faster than moving wires all over the drawing.
- Stops on Start release: inspect the holding branch, its endpoints, and the KM1 auxiliary contact.
- Still holds when Stop is pressed: find a coil supply path bypassing Stop.
- Picks up as soon as power is applied: check whether Start or the holding branch is already closed.
ELERUN LAB · TRY IT YOURSELF
Remove one contact to see what holding really does
Build the circuit above with the KM1 coil and its NO auxiliary contact sharing the same tag. Predict the state after pressing and releasing Start.
- In a test drawing, remove only the NO holding branch parallel to Start; leave Stop and the main path intact.
- In Run, what happens to KM1 while Start is held and after it is released? Point to the missing current path.
Compare your reasoning
Holding Start still feeds the KM1 coil through the main path. Releasing Start opens that path; with the auxiliary branch removed, no parallel path keeps the coil energized, so KM1 drops out. Reconnect the branch after Stop and before the coil, then retest.
This is a 24 VDC control-logic exercise in a test drawing, not an instruction to remove wiring from a running panel.
7. Frequently asked questions
Does the holding contact remember its state after a power loss?
No. In this circuit, loss of power releases the coil and opens its auxiliary contact. Restoring power with Start released leaves the circuit waiting for a new Start command.
Is the Stop button in this diagram an emergency stop?
No. It is the stop button of a basic control example. An emergency-stop function requires separate design and verification for the actual machine.
8. Manufacturer references
EleRun diagrams and exercises explain principles; they are not manufacturer-approved installation drawings.